Engineering Calculations for Adjustable
Support Bridge Assemblies
(For Rubber EcoCurbs)
| Subject:
Limited Engineering Calculations for
Adjustable Support Bridge Assemblies
as manufactured by
Advanced Support Products, Inc.
Date: November 7, 2000
Download
Download
|
Report done by:
M & Q Engineering, Inc.
1801 Kingwood Drive, Suite 250
Kingwood, Texas 77339 |
(fig. 1) Pipe Hanger Design Uplift Resistance
(figs. 2, 3 & 4) Typical Roof Loads Due to Gravity
Bearing Stresses
(fig. 2) Minimum Pipe Hanger Assembly
(fig. 3) Medium Pipe Hanger Assembly
(fig. 4) Maximum Pipe Hanger Assembly
(fig. 5) Product Information – Standard Bases
The data utilized for these calculations was obtained from Unistrut
for the structural assemblies and from Ginnell for the pipe hangers.
The information for the rubber molded bases was obtained from Advanced
Support Products, Inc. product Data.
The calculations performed are limited and only indicated the static
loads that would be exerted on a roof deck by the support assemblies
including standard sections of single or multiple lengths of pipe
conveying natural gas and water.
The piping and hanger assemblies in this report are considered "dead"
loads and should be taken into account during structural design of
the roof system. The hanger assembly loads in the attached tables
are intended to be used by the structural designer and provide the
information required to properly evaluate the complete roof system.
The products and their characteristics were tested by Advanced Support
Products, Inc. and represent the basis for our calculations. Roof
membrane system analysis as well as long term performance of the products
was not part of the calculation process. The following assumptions
were taken into account for the calculations:
- Placement of load on pipe supports was assumed to
be symmetrical
- Performance of the products at other than static loading
was not part of the calculation process.
- Hanger assemblies and piping were assumed to be placed
on a horizontal surface and pipe supports are normal to pipe.
Conclusions:
Based on our inspection and analysis of the product design, the load
capacity values at each point of support of the pipe hanger assemblies,
including the weight of piping are all less than the maximum allowable
stresses for typical roof deck insulations types currently in use
(5psi maximum). Therefore, the Adjustable Support Bridge Assemblies
as manufactured by Advanced Support Products, Inc. meet Factory Mutual
Research Corporation's recommendation that the design uplift resistance
for base should not exceed half of the ultimate design uplift resistance
of the roof cover system. The uplift resistance therefore, is dependent
on the uplift rating of the roof cover system.
(top)
(fig. 1) Pipe Hanger Design Uplift Resistance
| Advanced Support Products, Inc. Uplift
Resistance |
| Base Size |
FM Wind Uplift Rating |
| |
60 |
90 |
150 |
180 |
| 12” x 12” |
30 |
45 |
75 |
90 |
| 7.25” x 6” |
9.1 |
13.1 |
22.7 |
27.2 |
| 7.25” x 9” |
13.6 |
20.4 |
34.0 |
65.3 |
| 7.25” x 13” |
19.6 |
29.5 |
49.1 |
58.9 |
(fig. 2) Typical Roof Loads Due to Gravity Bearing Stresses
(Minimum Pipe Hanger Assembly)
| Curb Area: |
348 sq.in. |
| Curb Weight: |
32.0 lbs. |
| Frame Weight: |
29.0 lbs. |
| Hanger Weight: |
08.0 lbs. |
| Assembly Weight: |
69.0 lbs. 1 pipe
77.0 lbs. 2 pipes |
| Pipe Diameter |
Quantity |
Pipe Contents |
Pipe Support Spacing |
| 6 feet |
8 feet |
10 feet |
| 4 inch |
1 |
water |
167.0 lbs |
199.0 lbs. |
229.0 lbs |
| 0.48 psi |
0.57 psi |
0.66 psi |
| 2 |
water |
273.0 lbs |
337.0 lbs |
397.0 lbs |
| 0.78 psi |
0.97 psi |
1.14 psi |
| 6 inch |
1 |
water |
259.0 lbs |
319.0 lbs |
379.0 lbs |
| 0.74 psi |
0.92 psi |
1.09 psi |
| 2 |
water |
457.0 lbs |
577.0 lbs |
697.0 lbs |
| 1.31 psi |
1.66 psi |
2.00 psi |
The bearing stresses indicated above reflect utilization of an assembly
consisting of 4 each CCB 1806 Brace Bridges, 4 each CL 18 Channel
Legs and 2 each ACB 18 Adjustable Cross Bars.
(fig. 3) Typical Roof Loads Due to Gravity Bearing Stresses
(Medium Pipe Hanger Assembly)
| Curb Area: |
522 sq.in. |
| Curb Weight: |
48.0 lbs. |
| Frame Weight: |
29.0 lbs. |
| Hanger Weight: |
08.0 lbs. |
| Assembly Weight: |
85.0 lbs. 1 pipe
93.0 lbs. 2 pipe
101.0 lbs 3 pipes |
| Pipe Diameter |
Quantity |
Pipe Contents |
Pipe Support Spacing
|
| 6 feet |
8 feet |
10 feet |
| 4 inch |
1 |
Gas lbs
psi |
150 |
171 |
195 |
| 0.29 |
0.33 |
0.37 |
Water lbs
psi |
183 |
215 |
245 |
| 0.35 |
0.41 |
0.47 |
| 2 |
Gas lbs
psi |
223 |
265 |
313 |
| 0.43 |
0.51 |
0.60 |
Water lbs
psi |
289 |
353 |
413 |
| 0.55 |
0.68 |
0.79 |
| 3 |
Gas lbs
psi |
296 |
359 |
431 |
| 0.57 |
0.69 |
0.83 |
Water lbs
psi |
395 |
491 |
581 |
| 0.76 |
0.94 |
1.11 |
| 6 inch |
1 |
Gas lbs
psi |
195 |
235 |
275 |
| 0.37 |
0.45 |
0.53 |
Water lbs
psi |
275 |
335 |
395 |
| 0.53 |
0.64 |
0.76 |
| 2 |
Gas lbs
psi |
313 |
393 |
473 |
| 0.60 |
0.75 |
0.91 |
Water lbs
psi |
473 |
593 |
713 |
| 0.91 |
1.14 |
1.37 |
| 3 |
Gas lbs
psi |
431 |
551 |
671 |
| 0.83 |
1.06 |
1.29 |
Water lbs
psi |
671 |
851 |
1031 |
| 1.29 |
1.63 |
1.98 |
The bearing stresses indicated above reflect utilization of an assembly
consisting of 4 each CCB 1806 Brace Bridges, 4 each CL 18 Channel
Legs and 2 each ACB 18 Adjustable Cross Bars.
(top)
(fig. 4) Typical Roof Loads Due to Gravity Bearing Stresses
(Maximum Pipe Hanger Assembly)
| Curb Area: |
754 sq.in. |
| Curb Weight: |
80.0 lbs. |
| Frame Weight: |
29.0 lbs. |
| Hanger Weight: |
08.0 lbs. |
| Assembly Weight: |
117.0 lbs. 1 pipe
125.0 lbs. 2 pipe
133.0 lbs 3 pipes |
| Pipe Diameter |
Quantity |
Pipe Contents |
Pipe Support Spacing |
| 6 feet |
8 feet |
10 feet |
| 4 inch |
1 |
Gas lbs
psi |
182 |
203 |
227 |
| 0.29 |
0.27 |
0.30 |
Water lbs
psi |
215 |
247 |
277 |
| 0.29 |
0.33 |
0.37 |
| 2 |
Gas lbs
psi |
255 |
297 |
345 |
| 0.34 |
0.39 |
0.46 |
Water lbs
psi |
321 |
385 |
445 |
| 0.43 |
0.51 |
0.59 |
| 3 |
Gas lbs
psi |
328 |
391 |
463 |
| 0.44 |
0.52 |
0.61 |
Water lbs
psi |
427 |
523 |
613 |
| 0.57 |
0.69 |
0.81 |
| 6 inch |
1 |
Gas lbs
psi |
195 |
267 |
307 |
| 0.37 |
0.35 |
0.41 |
Water lbs
psi |
275 |
367 |
427 |
| 0.53 |
0.49 |
0.57 |
| 2 |
Gas lbs
psi |
313 |
425 |
505 |
| 0.60 |
0.56 |
0.91 |
Water lbs
psi |
473 |
625 |
745 |
| 0.91 |
0.83 |
0.99 |
| 3 |
Gas lbs
psi |
431 |
583 |
703 |
| 0.83 |
0.77 |
0.93 |
Water lbs
psi |
671 |
883 |
1063 |
| 1.29 |
1.17 |
1.41 |
| 8 inch |
1 |
Gas lbs
psi |
287 |
347 |
407 |
| 0.38 |
0.46 |
0.54 |
Water lbs
psi |
417 |
517 |
617 |
| 0.55 |
0.69 |
0.82 |
| 2 |
Gas lbs
psi |
465 |
585 |
705 |
| 0.62 |
0.78 |
0.94 |
Water lbs
psi |
725 |
925 |
1125 |
| 0.96 |
1.23 |
1.49 |
| 10 inch |
1 |
Gas lbs
psi |
357 |
437 |
527 |
| 0.47 |
0.58 |
0.70 |
Water lbs
psi |
567 |
717 |
867 |
| 0.75 |
0.95 |
1.15 |
| 2 |
Gas lbs
psi |
605 |
765 |
945 |
| 0.80 |
1.01 |
1.25 |
Water lbs
psi |
1025 |
1325 |
1625 |
| 1.36 |
1.76 |
2.16 |
| 12 inch |
1 |
Gas lbs
psi |
417 |
517 |
617 |
| 0.55 |
0.69 |
0.82 |
Water lbs
psi |
707 |
907 |
1107 |
| 0.94 |
1.20 |
1.47 |
The bearing stresses indicated above reflect utilization of
an assembly consisting of 4 each CCB 1806 Brace Bridges, 4 each CL
18 Channel Legs and 2 each ACB 18 Adjustable Cross Bars.
(top)
(fig. 5) Product Information - Standard Bases (Rubber)
| |
Minimum Base |
Medium Base |
Maximum Base |
| Size (inches) |
7.25 x 6 |
7.25 x 9 |
7.25 x 13 |
| Weight |
4 lbs. |
6 lbs. |
10 lbs. |
| Area |
43.50 sq.in. |
65.25 sq.in. |
94.25 sq.in. |
| Area per Support Bridge |
| 4 bases |
174 sq.in. |
261 sq.in. |
377 sq.in. |
| Area per Pipe Section |
| 8 bases |
348 sq.in. |
522 sq.in. |
754 sq.in. |